FDXM25F3V1B9 / RXM25N2V1B9 FDXM25F3V1B9 / RXM25N5V1B9 FDXM35F3V1B9 / RXM35N2V1B9 FDXM35F3V1B9 / RXM35N5V1B9 FDXM50F3V1B9 / RXM50N2V1B9 FDXM60F3V1B9 / RXM60N2V1B9
Indoor unit FDXM25F3V1B9 FDXM25F3V1B9 FDXM35F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V1B9
Outdoor unit RXM25N2V1B9 RXM25N5V1B9 RXM35N2V1B9 RXM35N5V1B9 RXM50N2V1B9 RXM60N2V1B9
Učin hlađenja Min. kW 1.30 1.30 1.40 1.40 1.70 1.70
  Min. Btu/h 4,435 4,435 4,800 4,800 5,800 5,800
  Min. Kcal/h 1,117 1,117 1,204 1,204 1,462 1,462
  Nom. kW 2.40 2.40 3.40 3.40 5.00 6.00
  Nom. Btu/h 8,189 8,189 11,600 11,600 17,100 20,500
  Nom. Kcal/h 2,064 2,064 2,923 2,923 4,299 5,159
  Maks. kW 3.00 3.00 3.80 3.80 5.30 6.50
  Maks. Btu/h 10,236 10,236 13,000 13,000 18,100 22,200
  Maks. Kcal/h 2,579 2,579 3,267 3,267 4,557 5,589
Učin grijanja Min. kW 1.30 1.30 1.40 1.40 1.70 1.70
  Min. Btu/h 4,435 4,435 4,800 4,800 5,800 5,800
  Min. Kcal/h 1,117 1,117 1,200 1,200 1,500 1,500
  Nom. kW 3.20 3.20 4.00 4.00 5.80 7.00
  Nom. Btu/h 10,919 10,919 13,600 13,600 19,800 23,900
  Nom. Kcal/h 2,752 2,752 3,439 3,439 4,987 6,019
  Maks. kW 4.50 4.50 5.00 5.00 6.00 7.10
  Maks. Btu/h 15,354 15,354 17,100 17,100 20,500 24,200
  Maks. Kcal/h 3,869 3,869 4,299 4,299 5,159 6,105
Ulazna snaga Hlađenje Nom. kW 0.64 0.64 1.14 1.14 1.63 2.05
  Grijanje Nom. kW 0.80 0.80 1.15 1.15 1.87 2.18
Nazivna učinkovitost EER   3.77 3.77 2.98 2.98 3.06 2.93
  COP   4.00 4.00 3.48 3.48 3.10 3.21
  Godišnja potrošnja energije kWh 318 318 570 570 817 1,024
  Direktiva o označivanju energetske učinkovitosti Hlađenje   A A C C B C
    Grijanje   A A B B D C
Hlađenje prostora Razred energetske učinkovitosti   A+ A+ A A A+ A
  Kapacitet Pdesign kW 2.40 2.40 3.40 3.40 5.00 6.00
  SEER   5.68 5.68 5.26 5.26 5.77 5.56
  Godišnja potrošnja energije kWh/a 148 148 226 226 303 378
  A stanje (35°C - 27/19) Pdc kW 2.40 2.40 3.40 3.40 5.00 6.00
    EERd   3.77 3.77 2.98 2.98 3.06 2.93
    Ulaz struje kW 0.64 0.64 1.14 1.14 1.63 2.05
  B stanje (30°C - 27/19) Pdc kW 1.76 1.76 2.50 2.50 3.67 4.43
    EERd   5.38 5.38 4.08 4.08 4.96 4.64
    Ulaz struje kW 0.33 0.33 0.61 0.61 0.74 0.95
  C stanje (25°C - 27/19) Pdc kW 1.27 1.27 1.61 1.61 2.37 2.85
    EERd   8.92 8.92 8.05 8.05 8.21 6.96
    Ulaz struje kW 0.14 0.14 0.20 0.20 0.29 0.41
  D stanje (20°C - 27/19) Pdc kW 1.31 1.31 1.46 1.46 2.26 2.26
    EERd   10.90 10.90 9.65 9.65 9.47 10.44
    Ulaz struje kW 0.12 0.12 0.15 0.15 0.24 0.22
Grijanje prostora (prosječna klima) Razred energetske učinkovitosti   A+ A+ A A A A
  Kapacitet Pdesign kW 2.60 2.60 2.90 2.90 4.00 4.60
  SCOP/A   4.24 4.24 3.88 3.88 3.93 3.80
  SCOPnet/A   4.27 4.27 3.91 3.91 3.95 3.83
  Pdh Heating capacity at -10° kW 2.16 2.16 2.41 2.41 3.56 3.94
  Godišnja potrošnja energije kWh/a 858 858 1,046 1,046 1,424 1,693
  Potrebna rezervna gornja granica grijanja u dizajniranim uvjetima kW 0.44 0.44 0.49 0.49 0.44 0.66
  TOL Tol (temperaturna granica rada) °C -15 -15 -15 -15 -15 -15
    Pdh (nazivna gornja granica grijanja) kW 1.93 1.93 2.15 2.15 3.59 3.72
    COPd (nazivni COP)   2.20 2.20 2.01 2.01 1.89 1.91
    Ulaz struje kW 0.88 0.88 1.07 1.07 1.90 1.95
  TBivalent Tbiv (bivalentna temperatura) °C -7 -7 -7 -7 -7 -7
    Pdh (nazivna gornja granica grijanja) kW 2.30 2.30 2.57 2.57 3.54 4.07
    COPd (nazivni COP)   2.81 2.81 2.60 2.60 2.87 2.58
    Ulaz struje kW 0.82 0.82 0.99 0.99 1.23 1.58
  A stanje (-7°C) Pdh (nazivna gornja granica grijanja) kW 2.30 2.30 2.57 2.57 3.54 4.07
    COPd (nazivni COP)   2.81 2.81 2.60 2.60 2.87 2.58
    Ulaz struje kW 0.82 0.82 0.99 0.99 1.23 1.58
  B stanje (2°C) Pdh (nazivna gornja granica grijanja) kW 1.40 1.40 1.57 1.57 2.13 2.48
    COPd (nazivni COP)   4.21 4.21 3.84 3.84 4.10 3.92
    Ulaz struje kW 0.33 0.33 0.41 0.41 0.52 0.63
  C stanje (7°C) Pdh (nazivna gornja granica grijanja) kW 1.00 1.00 1.02 1.02 1.62 1.62
    COPd (nazivni COP)   5.54 5.54 4.94 4.94 4.56 4.52
    Ulaz struje kW 0.18 0.18 0.21 0.21 0.36 0.36
  D stanje (12°C) Pdh (nazivna gornja granica grijanja) kW 1.17 1.17 1.19 1.19 1.92 1.92
    COPd (nazivni COP)   6.84 6.84 6.08 6.08 5.49 5.46
    Ulaz struje kW 0.17 0.17 0.20 0.20 0.35 0.35
Grijanje prostora (topla klima) Razred energetske učinkovitosti   A+++ A+++ A++ A++ A+ A+
  Kapacitet Pdesign kW 1.40 1.40 1.57 1.57 2.13 2.48
  SCOP   5.38 5.38 4.88 4.88 4.40 4.47
  SCOPnet   5.46 5.46 4.95 4.95 4.45 4.51
  Godišnja potrošnja energije kWh/a 365 365 450 450 679 777
  Potrebna kapica rezervnog grijača u uvjetima dizajna kW 0.00 0.00 0.00 0.00 0.00 0.00
  Kapacitet Tol (temperaturna granica rada) °C -15 -15 -15 -15 -15 -15
    Pdh (nazivna gornja granica grijanja) kW 1.93 1.93 2.15 2.15 3.59 3.72
    COPd (nazivni COP)   2.20 2.20 2.01 2.01 1.89 1.91
    Ulaz struje kW 0.88 0.88 1.07 1.07 1.90 1.95
  TBivalent Tbiv (bivalentna temperatura) °C 2 2 2 2 2 2
    Pdh (nazivna gornja granica grijanja) kW 1.40 1.40 1.57 1.57 2.13 2.48
    COPd (nazivni COP)   4.21 4.21 3.84 3.84 4.10 3.92
    Ulaz struje kW 0.33 0.33 0.41 0.41 0.52 0.63
  B stanje (2°C) Pdh (nazivna gornja granica grijanja) kW 1.40 1.40 1.57 1.57 2.13 2.48
    COPd (nazivni COP)   4.21 4.21 3.84 3.84 4.10 3.92
    Ulaz struje kW 0.33 0.33 0.41 0.41 0.52 0.63
  C stanje (7°C) Pdh (nazivna gornja granica grijanja) kW 1.00 1.00 1.02 1.02 1.62 1.62
    COPd (nazivni COP)   5.54 5.54 4.94 4.94 4.56 4.52
    Ulaz struje kW 0.18 0.18 0.21 0.21 0.36 0.36
  D stanje (12°C) Pdh (nazivna gornja granica grijanja) kW 1.17 1.17 1.19 1.19 1.92 1.92
    COPd (nazivni COP)   6.84 6.84 6.08 6.08 5.49 5.46
    Ulaz struje kW 0.17 0.17 0.20 0.20 0.35 0.35
Potrošnja energije u drugim načinima rada osim aktivnog Crankcase heater mode Cooling PCK kW     0.000 0.000 0.000 0.000
    Heating PCK kW     0.000 0.000 0.000 0.000
  Isključeni način rada Hlađenje POFF kW 14.0 14.0 0.014 0.014 0.015 0.015
    Grijanje POFF kW 14.0 14.0 0.014 0.014 0.015 0.015
  Način rada u stanju mirovanja Hlađenje PSB kW 14.0 14.0 0.014 0.014 0.015 0.015
    Grijanje PSB kW 14.0 14.0 0.014 0.014 0.015 0.015
  Isključeni način rada termostata Hlađenje PTO kW 7.0 7.0 0.007 0.007 0.009 0.009
    Grijanje PTO kW 7.0 7.0 0.007 0.007 0.009 0.009
Rashladna tehnika Cdc (hlađenje razgradnjom)   0.25 0.25 0.25 0.25 0.25 0.25
Grijanje Cdh (grijanje razgradnjom)   0.25 0.25 0.25 0.25 0.25 0.25
Uključujući funkciju hlađenja Da Da Da Da Da Da
Uključujući funkciju grijanja Da Da Da Da Da Da
Uključujući prosječnu klimu Da Da Da Da Da Da
Uključujući hladnu sezonu Ne Ne Ne Ne Ne Ne
Uključujući toplu sezonu Da Da Da Da Da Da
Logotip eko naljepnice Ne Ne        
Eurovent Sound power level outdoor Cooling Nom. dBA 59 59 61 61 62 63
  Unutarnja razina jačine zvuka Hlađenje Nom. dBA 53 53 53 53 55 56
  Duljina cjevovoda Hlađenje Uvjeti mjerenja m 5.0 5.0 5.00 5.00 5.00 5.00
Napomene (1) - Vidi električne podatke na posebnim nacrtima (1) - Vidi električne podatke na posebnim nacrtima (1) - Nom. kapacitet hlađenja se temelji se na sljedećim parametrima: unutarnja temperatura: 27 °C DB, 19 °C WB, vanjska temperatura: 35 °C DB, odgovarajuće cijevi rashladnog sredstva: 5 m, razlika u visini: 0m. (1) - Nom. kapacitet hlađenja se temelji se na sljedećim parametrima: unutarnja temperatura: 27 °C DB, 19 °C WB, vanjska temperatura: 35 °C DB, odgovarajuće cijevi rashladnog sredstva: 5 m, razlika u visini: 0m. (1) - Nom. kapacitet hlađenja se temelji se na sljedećim parametrima: unutarnja temperatura: 27 °C DB, 19 °C WB, vanjska temperatura: 35 °C DB, odgovarajuće cijevi rashladnog sredstva: 5 m, razlika u visini: 0m. (1) - Nom. kapacitet hlađenja se temelji se na sljedećim parametrima: unutarnja temperatura: 27 °C DB, 19 °C WB, vanjska temperatura: 35 °C DB, odgovarajuće cijevi rashladnog sredstva: 5 m, razlika u visini: 0m.
  (2) - Pogledajte odvojene nacrte za radno područje (2) - Pogledajte odvojene nacrte za radno područje (2) - Nazivni učin grijanja zasnovani su na: unutarnja temperatura: 20°C DB, vanjska temperatura : 7°C DB, 6°C WB, odgovarajući cjevovod za radnu tvar: 5 m, razlika razine: 0 m. (2) - Nazivni učin grijanja zasnovani su na: unutarnja temperatura: 20°C DB, vanjska temperatura : 7°C DB, 6°C WB, odgovarajući cjevovod za radnu tvar: 5 m, razlika razine: 0 m. (2) - Nazivni učin grijanja zasnovani su na: unutarnja temperatura: 20°C DB, vanjska temperatura : 7°C DB, 6°C WB, odgovarajući cjevovod za radnu tvar: 5 m, razlika razine: 0 m. (2) - Nazivni učin grijanja zasnovani su na: unutarnja temperatura: 20°C DB, vanjska temperatura : 7°C DB, 6°C WB, odgovarajući cjevovod za radnu tvar: 5 m, razlika razine: 0 m.
  (3) - Nom. kapacitet hlađenja se temelji se na sljedećim parametrima: unutarnja temperatura: 27 °C DB, 19 °C WB, vanjska temperatura: 35 °C DB, odgovarajuće cijevi rashladnog sredstva: 5 m, razlika u visini: 0m. (3) - Nominalan kapacitet hlađenja se temelji se na sljedećim parametrima: unutarnja temperatura: 27 °C DB, 19 °C WB, vanjska temperatura: 35 °C DB, odgovarajuće cijevi rashladnog sredstva: 5 m, razlika u visini: 0m. (3) - Pogledajte odvojene nacrte za radno područje (3) - Pogledajte odvojene nacrte za radno područje (3) - Pogledajte odvojene nacrte za radno područje (3) - Pogledajte odvojene nacrte za radno područje
  (4) - Nazivni učin grijanja zasnovani su na: unutarnja temperatura: 20°C DB, vanjska temperatura : 7°C DB, 6°C WB, odgovarajući cjevovod za radnu tvar: 5 m, razlika razine: 0 m. (4) - Nazivni učin grijanja zasnovani su na: unutarnja temperatura: 20°C DB, vanjska temperatura : 7°C DB, 6°C WB, odgovarajući cjevovod za radnu tvar: 5 m, razlika razine: 0 m. (4) - Vidi električne podatke na posebnim nacrtima (4) - Vidi električne podatke na posebnim nacrtima (4) - Vidi električne podatke na posebnim nacrtima (4) - Vidi električne podatke na posebnim nacrtima