Specifications Table for EHVH-CB / ERLQ-CW1

EHVH11S18CB3V / ERLQ011CAW1 EHVH11S26CB9W / ERLQ011CAW1 EHVH16S26CB9W / ERLQ014CAW1 EHVH16S18CB3V / ERLQ014CAW1 EHVH16S18CB3V / ERLQ016CAW1 EHVH16S26CB9W / ERLQ016CAW1
Učin grijanja Nom. kW 11.2 (1), 11.0 (2) 11.2 (1), 11.0 (2) 14.5 (1), 13.6 (2) 14.5 (1), 13.6 (2) 16.0 (1), 15.2 (2) 16.0 (1), 15.2 (2)
  Maks. kW 8.60 (3), 8.60 (4) 8.60 (3), 8.60 (4) 10.6 (3), 10.8 (4) 10.6 (3), 10.8 (4) 11.4 (3), 10.9 (4) 11.4 (3), 10.9 (4)
Ulazna snaga Grijanje Nom. kW 3.42 (1), 4.21 (2) 3.42 (1), 4.21 (2) 3.37 (1), 4.10 (2) 3.37 (1), 4.10 (2) 3.76 (1), 4.66 (2) 3.76 (1), 4.66 (2)
    Maks. kW 3.13 (3), 4.10 (4) 3.13 (3), 4.10 (4) 4.00 (3), 5.19 (4) 4.00 (3), 5.19 (4) 4.32 (3), 5.22 (4) 4.32 (3), 5.22 (4)
COP 4.60 (1), 2.75 (3), 3.55 (2), 2.10 (4) 4.60 (1), 2.75 (3), 3.55 (2), 2.10 (4) 4.30 (1), 2.65 (3), 3.32 (2), 2.08 (4) 4.30 (1), 2.65 (3), 3.32 (2), 2.08 (4) 4.25 (1), 2.64 (3), 3.26 (2), 2.09 (4) 4.25 (1), 2.64 (3), 3.26 (2), 2.09 (4)
Pumpa Nominalna ESP jedinica Grijanje kPa 34.2 (7), 35.9 (8) 34.2 (7), 35.9 (8) 43.2 (7), 51.2 (8) 43.2 (7), 51.2 (8) 26.8 (7), 36.3 (8) 26.8 (7), 36.3 (8)
Izmjenjivač topline na vodenoj strani Količina vode u cirkulaciji Grijanje Nom. l/min 32.1 (7), 31.5 (8) 32.1 (7), 31.5 (8) 41.6 (7), 39.0 (8) 41.6 (7), 39.0 (8) 45.9 (7), 43.6 (8) 45.9 (7), 43.6 (8)
Općenito Detalji o dobavljaču/proizvođaču Name and address   Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
    Naziv ili trgovački znak   Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V.
  Opis proizvoda Dizalica topline zrak-voda   Da Da Da Da Da Da
    Dizalica topline rasolina-u-vodu   Ne Ne Ne Ne Ne Ne
    Dizalica topline u kombinaciji s grijačem   Da Da Da Da Da Da
    Niskotemperaturna dizalica topline   Ne Ne Ne Ne Ne Ne
    Ugrađeni dodatni grijač   Da Da Da Da Da Da
    Dizalica topline voda-voda   Ne Ne Ne Ne Ne Ne
  LW(A) Razina zvučne snage (u skladu s EN14825) Unutarnja dB(A) 42.0 42.0 44.0 44.0 44.0 44.0
LW(A) Razina zvučne snage (u skladu s EN14825) Vanjska dB(A) 64.0 64.0 64.0 64.0 66.0 66.0
Zvučna snaga u uvjetu Eko-dizajna i oznaka energetske učinkovitosti Zvučna snaga u režimu grijanja mjerena je prema EN12102 u uvjetima EN14825 Zvučna snaga u režimu grijanja mjerena je prema EN12102 u uvjetima EN14825 Zvučna snaga u režimu grijanja mjerena je prema EN12102 u uvjetima EN14825 Zvučna snaga u režimu grijanja mjerena je prema EN12102 u uvjetima EN14825 Zvučna snaga u režimu grijanja mjerena je prema EN12102 u uvjetima EN14825 Zvučna snaga u režimu grijanja mjerena je prema EN12102 u uvjetima EN14825
Tank Name   Spremnik potrošne tople vode od nehrđajućeg čelika od 180 litara Spremnik potrošne tople vode od nehrđajućeg čelika od 260 litara Spremnik potrošne tople vode od nehrđajućeg čelika od 260 litara Spremnik potrošne tople vode od nehrđajućeg čelika od 180 litara Spremnik potrošne tople vode od nehrđajućeg čelika od 180 litara Spremnik potrošne tople vode od nehrđajućeg čelika od 260 litara
Općenito grijanje prostora Zrak-voda jedinica Nazivni protok zraka (vanjska jedinica) m³/h 5,400 5,400 5,400 5,400 5,400 5,400
  Ostalo Regulacija učina   Inverter Inverter Inverter Inverter Inverter Inverter
    Cdh (grijanje razgradnjom)   1.00 1.00 1.00 1.00 1.00 1.00
    Pck (grijač kućišta kolj. osovine) kW 0.055 0.055 0.055 0.055 0.055 0.055
    Poff (režim isključeno) kW 0.055 0.055 0.055 0.055 0.055 0.055
    Psb (načina rada u stanju mirovanja) kW 0.055 0.055 0.055 0.055 0.055 0.055
    Pto (termostat isključen) kW 0.057 0.057 0.057 0.057 0.057 0.057
  Ugrađeni dodatni grijač NOx emisija mg/kWh 0.00 0.00 0.00 0.00 0.00 0.00
    Psup kW 3.00 9.00 9.00 3.00 3.00 9.00
    Vrsta ulazne energije   Električni Električni Električni Električni Električni Električni
Grijanje potrošne tople vode Općenito Deklarirani profil opterećenja   L XL XL L L XL
    Funkcija za utvrđivanje grijanja vode tijekom sati jeftinije električne energije   Da Da Da Da Da Da
  Prosječni klimatski uvjeti AEC (godišnja potrošnja električne energije) kWh 1,170 1,720 1,720 1,170 1,170 1,720
    AFC (godišnja potrošnja goriva) Gj 0.00          
    Ƞwh (water heating efficiency) % 87.4 97.7 97.7 87.4 87.4 97.7
    Qelec (dnevna potrošnja električne energije) kWh 5.32 7.83 7.83 5.32 5.32 7.83
    Qfuel (dnevna potrošnja goriva) kWh 0.00          
    Razred energetske učinkovitosti grijanja vode   A A A A A A
  Hladni klimatski uvjeti AEC (godišnja potrošnja električne energije) kWh 1,340 1,980 1,980 1,340 1,340 1,980
    AFC(godišnja potrošnja goriva) Gj 0.00          
    Ƞwh (učinkovitost grijanja vode) % 76.6 85.1 85.1 76.6 76.6 85.1
    Qelec (dnevna potrošnja električne energije) kWh 6.08 8.99 8.99 6.08 6.08 8.99
    Qfuel (dnevna potrošnja goriva) kWh 0.00          
  Topli klimatski uvjeti AEC (godišnja potrošnja električne energije) kWh 1,110 1,630 1,630 1,110 1,110 1,630
    AFC (godišnja potrošnja goriva) Gj 0.00          
    Ƞwh (učinkovitost grijanja vode) % 92.3 103 103 92.3 92.3 103
    Qelec (dnevna potrošnja električne energije) kWh 5.04 7.40 7.40 5.04 5.04 7.40
    Qfuel (dnevna potrošnja goriva) kWh 0.00          
Grijanje prostora Izlaz za vodu u prosječnoj klimi 55°C Općenito SCOP   3.09          
      Godišnja potrošnja energije kWh 6,260          
      Ƞs (sezonska učinkovitost grijanja prostora) % 120          
      Pnazivno pri -10°C kW 9.99          
      Qhe Godišnja potrošnja energije (GCV) Gj 22.6          
      Razred sezonske učinkovitosti grijanja prostora   A+          
    Stanje (-7 °C DB/-8 °C WB) Cdh (grijanje razgradnjom)   1.00          
      COPd   1.99          
      Pdh kW 8.83          
      PERd % 79.6          
    B Stanje (2 °C DB/1 °C WB) Cdh (grijanje razgradnjom)   1.00          
      COPd   3.24          
      Pdh kW 5.28          
      PERd % 130          
    C Stanje (7 °C DB/6 °C WB) Cdh (grijanje razgradnjom)   0.950          
      COPd   4.31          
      Pdh kW 4.47          
      PERd % 172          
    C Stanje (12 °C DB/11 °C WB) Cdh (grijanje razgradnjom)   0.930          
      COPd   6.41          
      Pdh kW 5.37          
      PERd % 256          
    Tol (granična radna temperatura) COPd   1.79          
      Pdh kW 9.08          
      PERd % 71.6          
      TOL °C -10.0          
      WTOL °C 55.0          
    Dopunski toplinski učin na izlazu Psup (pri Tdesign -10°C) kW 0.910          
    Tbiv (bivalentna temperatura) COPd   1.99          
      Pdh kW 8.83          
      PERd % 79.6          
      Tbiv °C -7.00          
  Izlaz za vodu u hladnoj klimi 55°C Općenito Godišnja potrošnja energije kWh 6,740          
      Ƞs (sezonska učinkovitost grijanja prostora) % 95.0          
      Pnazivno pri -22°C kW 6.99          
      Qhe Godišnja potrošnja energije (GCV) Gj 24.3          
  Izlaz za vodu u toploj klimi 55 °C Općenito Godišnja potrošnja energije kWh 2,630          
      Ƞs (sezonska učinkovitost grijanja prostora) % 125          
      Pnazivno pri 2°C kW 7.58          
      Qhe Godišnja potrošnja energije (GCV) Gj 9.47          
  Izlaz za vodu u prosječnoj klimi 35°C Općenito SCOP   3.98          
      Godišnja potrošnja energije kWh 5,380          
      Ƞs (sezonska učinkovitost grijanja prostora) % 156          
      Pnazivno pri -10°C kW 11.2          
      Qhe Godišnja potrošnja energije (GCV) Gj 19.4          
      Razred sezonske učinkovitosti grijanja prostora   A++          
    Stanje (-7 °C DB/-8 °C WB) COPd   2.63          
      Pdh kW 8.88          
      PERd % 105          
    B Stanje (2 °C DB/1 °C WB) Cdh (grijanje razgradnjom)   1.00          
      COPd   4.05          
      Pdh kW 6.03          
      PERd % 162          
    C Stanje (7 °C DB/6 °C WB) Cdh (grijanje razgradnjom)   0.940          
      COPd   6.77          
      Pdh kW 5.74          
      PERd % 271          
    C Stanje (12 °C DB/11 °C WB) Cdh (grijanje razgradnjom)   0.920          
      COPd   8.97          
      Pdh kW 6.50          
      PERd % 359          
    Tol (granična radna temperatura) COPd   2.34          
      Pdh kW 8.76          
      PERd % 93.6          
      TOL °C -10.0          
      WTOL °C 35.0          
    Tbiv (bivalentna temperatura) COPd   2.82          
      Pdh kW 9.09          
      PERd % 113          
      Tbiv °C -5.00          
    Dopunski toplinski učin na izlazu Psup (pri Tdesign -10°C) kW 2.44          
  Izlaz za vodu u hladnoj klimi 35 °C Općenito Godišnja potrošnja energije kWh 6,430          
      Ƞs (sezonska učinkovitost grijanja prostora) % 148          
      Pnazivno pri -22°C kW 10.3          
      Qhe Godišnja potrošnja energije (GCV) Gj 23.1          
  Izlaz za vodu u toploj klimi 35°C Općenito Godišnja potrošnja energije kWh 1,950          
      Ƞs (sezonska učinkovitost grijanja prostora) % 192          
      Pnazivno pri 2°C kW 9.06          
      Qhe Godišnja potrošnja energije (GCV) Gj 7.02          
Napomene Stanje 1: hlađenje Ta 35°C - LWE 18°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Stanje 1: hlađenje Ta 35°C - LWE 18°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Stanje 1: hlađenje Ta 35°C - LWE 18°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Stanje 1: hlađenje Ta 35°C - LWE 18°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Stanje 1: hlađenje Ta 35°C - LWE 18°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Stanje 1: hlađenje Ta 35°C - LWE 18°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
  Stanje 2: hlađenje Ta 35°C - LWE 7°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Stanje 2: hlađenje Ta 35°C - LWE 7°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Stanje 2: hlađenje Ta 35°C - LWE 7°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Stanje 2: hlađenje Ta 35°C - LWE 7°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Stanje 2: hlađenje Ta 35°C - LWE 7°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Stanje 2: hlađenje Ta 35°C - LWE 7°C (DT = 5°C); grijanje Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C)
  Stanje 3: grijanje Ta DB -7°C (RH85%) - LWC 35°C (3) - Stanje 3: grijanje Ta DB -7°C (RH85%) - LWC 35°C (3) - Stanje 3: grijanje Ta DB -7°C (RH85%) - LWC 35°C (3) - Stanje 3: grijanje Ta DB -7°C (RH85%) - LWC 35°C (3) - Stanje 3: grijanje Ta DB -7°C (RH85%) - LWC 35°C (3) - Stanje 3: grijanje Ta DB -7°C (RH85%) - LWC 35°C
  Stanje 4: grijanje Ta DB -7°C (RH85%) - LWC 45°C (4) - Stanje 4: grijanje Ta DB -7°C (RH85%) - LWC 45°C (4) - Stanje 4: grijanje Ta DB -7°C (RH85%) - LWC 45°C (4) - Stanje 4: grijanje Ta DB -7°C (RH85%) - LWC 45°C (4) - Stanje 4: grijanje Ta DB -7°C (RH85%) - LWC 45°C (4) - Stanje 4: grijanje Ta DB -7°C (RH85%) - LWC 45°C
  Tamb 35°C - LWE 7°C (DT=5°C) (5) - Tamb 35°C - LWE 7°C (DT=5°C) (5) - Tamb 35°C - LWE 7°C (DT=5°C) (5) - Tamb 35°C - LWE 7°C (DT=5°C) (5) - Tamb 35°C - LWE 7°C (DT=5°C) (5) - Tamb 35°C - LWE 7°C (DT=5°C)
  Tamb 35°C - LWE 18°C (DT=5°C) (6) - Tamb 35°C - LWE 18°C (DT=5°C) (6) - Tamb 35°C - LWE 18°C (DT=5°C) (6) - Tamb 35°C - LWE 18°C (DT=5°C) (6) - Tamb 35°C - LWE 18°C (DT=5°C) (6) - Tamb 35°C - LWE 18°C (DT=5°C)
  DB/WB 7°C/6°C-LWC 35°C(DT=5°C) (7) - DB/WB 7°C/6°C-LWC 35°C(DT=5°C) (7) - DB/WB 7°C/6°C-LWC 35°C(DT=5°C) (7) - DB/WB 7°C/6°C-LWC 35°C(DT=5°C) (7) - DB/WB 7°C/6°C-LWC 35°C(DT=5°C) (7) - DB/WB 7°C/6°C-LWC 35°C(DT=5°C)
  DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (8) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (8) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (8) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (8) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (8) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
Grijanje prostora Izlaz za vodu u prosječnoj klimi 55°C Općenito Godišnja potrošnja energije kWh   6,260 7,900 7,900 8,970 8,970
      Ƞs (sezonska učinkovitost grijanja prostora) %   120 123 123 119 119
      Pnazivno pri -10°C kW   9.99 12.7 12.7 13.9 13.9
      Qhe Godišnja potrošnja energije (GCV) Gj   22.6 28.4 28.4 32.3 32.3
      SCOP     3.09 3.16 3.16 3.06 3.06
      Razred sezonske učinkovitosti grijanja prostora     A+ A+ A+ A+ A+
    Stanje (-7 °C DB/-8 °C WB) Cdh (grijanje razgradnjom)     1.00 1.00 1.00 1.00 1.00
      COPd     1.99 1.76 1.76 1.78 1.78
      Pdh kW   8.83 9.97 9.97 12.2 12.2
      PERd %   79.6 70.4 70.4 71.2 71.2
    B Stanje (2 °C DB/1 °C WB) Cdh (grijanje razgradnjom)     1.00 1.00 1.00 1.00 1.00
      COPd     3.24 3.55 3.55 3.12 3.12
      Pdh kW   5.28 6.76 6.76 7.61 7.61
      PERd %   130 142 142 125 125
    C Stanje (7 °C DB/6 °C WB) Cdh (grijanje razgradnjom)     0.950 0.950 0.950 1.00 1.00
      COPd     4.31 4.22 4.22 4.40 4.40
      Pdh kW   4.47 4.66 4.66 4.83 4.83
      PERd %   172 169 169 176 176
    C Stanje (12 °C DB/11 °C WB) Cdh (grijanje razgradnjom)     0.930 0.940 0.940 0.930 0.930
      COPd     6.41 5.44 5.44 6.36 6.36
      Pdh kW   5.37 5.26 5.26 5.38 5.38
      PERd %   256 218 218 254 254
    Tol (granična radna temperatura) COPd     1.79 1.75 1.75 1.71 1.71
      Pdh kW   9.08 12.2 12.2 13.3 13.3
      PERd %   71.6 70.0 70.0 68.4 68.4
      TOL °C   -10.0 -10.0 -10.0 -10.0 -10.0
      WTOL °C   55.0 55.0 55.0 55.0 55.0
    Dopunski toplinski učin na izlazu Psup (pri Tdesign -10°C) kW   0.910 0.550 0.550 0.580 0.580
    Tbiv (bivalentna temperatura) COPd     1.99 1.92 1.92 1.78 1.78
      Pdh kW   8.83 11.0 11.0 12.2 12.2
      PERd %   79.6 76.8 76.8 71.2 71.2
      Tbiv °C   -7.00 -6.00 -6.00 -7.00 -7.00
  Izlaz za vodu u hladnoj klimi 55°C Općenito Godišnja potrošnja energije kWh   6,740 7,870 7,870 8,580 8,580
      Ƞs (sezonska učinkovitost grijanja prostora) %   95.0 95.5 95.5 98.3 98.3
      Pnazivno pri -22°C kW   6.99 8.15 8.15 9.12 9.12
      Qhe Godišnja potrošnja energije (GCV) Gj   24.3 28.3 28.3 30.9 30.9
  Izlaz za vodu u toploj klimi 55 °C Općenito Godišnja potrošnja energije kWh   2,630 3,270 3,270 3,420 3,420
      Ƞs (sezonska učinkovitost grijanja prostora) %   125 135 135 136 136
      Pnazivno pri 2°C kW   7.58 9.84 9.84 10.3 10.3
      Qhe Godišnja potrošnja energije (GCV) Gj   9.47 11.8 11.8 12.3 12.3
  Izlaz za vodu u prosječnoj klimi 35°C Općenito SCOP     3.98 3.90 3.90 3.80 3.80
      Godišnja potrošnja energije kWh   5,380 7,250 7,250 8,270 8,270
      Ƞs (sezonska učinkovitost grijanja prostora) %   156 153 153 149 149
      Pnazivno pri -10°C kW   11.2 14.5 14.5 16.0 16.0
      Qhe Godišnja potrošnja energije (GCV) Gj   19.4 26.1 26.1 29.8 29.8
      Razred sezonske učinkovitosti grijanja prostora     A++ A++ A++ A+ A+
    Stanje (-7 °C DB/-8 °C WB) COPd     2.63 2.63 2.63 2.33 2.33
      Pdh kW   8.88 10.7 10.7 12.4 12.4
      PERd %   105 105 105 93.2 93.2
    B Stanje (2 °C DB/1 °C WB) Cdh (grijanje razgradnjom)     1.00 1.00 1.00 1.00 1.00
      COPd     4.05 4.07 4.07 3.74 3.74
      Pdh kW   6.03 7.71 7.71 8.62 8.62
      PERd %   162 163 163 150 150
    C Stanje (7 °C DB/6 °C WB) Cdh (grijanje razgradnjom)     0.940 1.00 1.00 0.940 0.940
      COPd     6.77 5.71 5.71 6.77 6.77
      Pdh kW   5.74 5.05 5.05 5.74 5.74
      PERd %   271 228 228 271 271
    C Stanje (12 °C DB/11 °C WB) Cdh (grijanje razgradnjom)     0.920 0.930 0.930 0.920 0.920
      COPd     8.97 6.71 6.71 8.97 8.97
      Pdh kW   6.50 5.16 5.16 6.50 6.50
      PERd %   359 268 268 359 359
    Tol (granična radna temperatura) COPd     2.34 2.60 2.60 2.05 2.05
      Pdh kW   8.76 12.6 12.6 11.7 11.7
      PERd %   93.6 104 104 82.0 82.0
      TOL °C   -10.0 -10.0 -10.0 -10.0 -10.0
      WTOL °C   35.0 35.0 35.0 35.0 35.0
    Tbiv (bivalentna temperatura) COPd     2.82 2.83 2.83 2.56 2.56
      Pdh kW   9.09 11.6 11.6 12.1 12.1
      PERd %   113 113 113 102 102
      Tbiv °C   -5.00 -5.00 -5.00 -4.00 -4.00
    Dopunski toplinski učin na izlazu Psup (pri Tdesign -10°C) kW   2.44 1.93 1.93 4.35 4.35
  Izlaz za vodu u hladnoj klimi 35 °C Općenito Godišnja potrošnja energije kWh   6,430 8,170 8,170 9,050 9,050
      Ƞs (sezonska učinkovitost grijanja prostora) %   148 141 141 137 137
      Pnazivno pri -22°C kW   10.3 12.3 12.3 13.3 13.3
      Qhe Godišnja potrošnja energije (GCV) Gj   23.1 29.4 29.4 32.6 32.6
  Izlaz za vodu u toploj klimi 35°C Općenito Godišnja potrošnja energije kWh   1,950 2,350 2,350 2,480 2,480
      Ƞs (sezonska učinkovitost grijanja prostora) %   192 199 199 199 199
      Pnazivno pri 2°C kW   9.06 10.9 10.9 11.4 11.4
      Qhe Godišnja potrošnja energije (GCV) Gj   7.02 8.46 8.46 8.92 8.92